Viessmann Boiler: LON cabling for longer runs (continued)

Updated · by Aurora Star Tech Inc.

LON cabling for longer runs (continued) on a Viessmann boiler: Continuation of the LON layouts with on-site cable and LON plugs or junction boxes.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 300 GW6B, LON network

How to fix lon cabling for longer runs (continued): step by step

  1. For runs up to 3000 ft (900 m), use LON plugs with on-site cable, up to 30 participants.
  2. For runs up to 3000 ft (900 m) with junction boxes, use LON cable 23 ft (7 m) to the sockets and on-site cable between sockets.
  3. Place the terminal end resistor at the far end of the line.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitotronic 300 GW6B installation and service manual, p. 47. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.