Viessmann Boiler: Limit maximum heating input
Limit maximum heating input on a Viessmann boiler: Heating input can be capped through the modulation range. This does not affect domestic hot water heating.
Applies to: Vitodens 100-W, WB1B
How to fix limit maximum heating input: step by step
- Start up the boiler.
- Turn selector dial tr clockwise to U Reset, then back to the middle range within 2 seconds and on to position 6 to enter high-fire test. SERV, water temperature, five flashing bars and A show.
- With selector dial tr, choose a value from 1 to 6 for the required percentage of rated input. For example, position 1 shows one flashing bar and reduces input to 40% of max.
- Turn the water temperature selector dial clockwise within 2 seconds and back into the operating range. The icon flashes briefly to confirm the setting was accepted.
- Press the ON/OFF switch and start the boiler. The maximum input is now set.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 65. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.