Updated · by Aurora Star Tech Inc.

Keeping lead boiler section valves open on a Viessmann boiler: When the burners are off and all boiler section valves are closed, system venting is no longer guaranteed. The lead boiler's section valves can be held open by an external request.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Lead boiler section valves

How to fix keeping lead boiler section valves open: step by step

  1. Insert an EA1 extension with a fixed jumper at input DE1.
  2. Send a request from the building management system at the 0-10 V input, for example 2 V (68°F / 20°C).
  3. Alternatively, send a floating contact request to plug aVH (terminals 2-3).
  4. Set master coding 5D to 2 and 9B to 1.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 installation instructions, p. 33. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.