Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Installing and wiring the outdoor temperature sensor

Updated · by Aurora Star Tech Inc.

Installing and wiring the outdoor temperature sensor on a Viessmann boiler: Mounting and wiring the outdoor sensor to the boiler control board, including cable limits and placement rules.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Models 45, 60

How to fix installing and wiring the outdoor temperature sensor: step by step

  1. Remove the cover of the outdoor temperature sensor.
  2. Mount the wall-mount base with the cable entry pointing downward.
  3. Route the cable from the boiler control board to the outdoor sensor and connect it to the sensor terminals (wires are interchangeable).
  4. Connect the outdoor sensor to terminals X3.1/X3.2 on the boiler control board (wires are interchangeable).
  5. Place the cover on the base and snap it into place.
  6. Cable: 2-wire, max. 95 ft (35 m), minimum AWG 16 copper.
  7. Mount the sensor 6.6 to 8.2 ft (2 to 2.5 m) above ground on the north or northwest wall.
  8. On a multi-storey building, mount it in the upper half of the second floor.
  9. Keep the sensor away from windows, doors, air vents, balconies and gutters.
  10. Do not cover the sensor with plaster; allow for plaster thickness or remove the sensor before plastering.
  11. Keep the sensor cable away from line voltage wiring (120/240 V).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 49. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.