Viessmann Boiler: Install valve adaptor for boiler return mixing or modulating valve
Install valve adaptor for boiler return mixing or modulating valve on a Viessmann boiler: Wiring a 120V or 24V valve actuator through the valve adaptor.
Applies to: VD2/VD2A/CT3 and CM2 valve adaptors
How to fix install valve adaptor for boiler return mixing or modulating valve: step by step
- Disconnect power to the control.
- Mount the 120V or 24V valve adaptor on the DIN rail inside the connection enclosure.
- Insert plug gS into socket gS on the control.
- Secure the cable with a tie.
- Connect the black adaptor wire to the aBH connection on the DIN rail (VD2: terminal 8, 9 or 10; CM2: 120V L out, terminal 10, 11 or 12).
- Connect the valve actuator wires to the adaptor terminals as shown in the figures.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitocontrol-S VD2/CT3/CM2
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Vitotronic 100 GC1
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, pp. 47-48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.