Viessmann Boiler: Install the condensate drain

Updated · by Aurora Star Tech Inc.

Install the condensate drain on a Viessmann boiler: The boiler has a built-in condensate trap, so no external trap is needed when using flexible discharge tubing. Drain must be sloped and must not siphon the boiler.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

Common causes of install the condensate drain

  • Condensate outlet below the drain point, which needs a pump
  • Discharge tubing pushed up into the housing as shipped

How to fix install the condensate drain: step by step

  1. Use 1 in. (25 mm) field-supplied discharge tubing.
  2. Use CPVC or PVC approved by the listed codes. Drain pipe and fittings must meet ANSI, ASTM D1785 or D2846. Cement and primer must meet ASTM D2564 or F493. In Canada use CSA or ULC listed schedule 40 CPVC or PVC.
  3. If the condensate outlet is lower than the drain, install a condensate pump approved for condensing boilers. Choose a pump with an overflow switch.
  4. Terminate the drain into an open or vented drain as close to the boiler as possible to prevent siphoning.
  5. Install the drain pipe with a suitable gradient and pull the hose out of the boiler so no unnecessary bends form inside.
  6. Pull the flexible discharge tubing down so condensate can drain.
  7. Check that siphon connection A is tight.
  8. Keep pipe ventilation between the siphon trap and any neutralization unit.
  9. Do not connect drains from other appliances, such as a water softener backwash, into the condensate line.
  10. Discharge condensate to the drain system directly or through a neutralization unit (accessory) if required.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitodens 222-F, B2TB installation instructions, p. 22. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.