Viessmann Boiler: Install the condensate drain and siphon
Install the condensate drain and siphon on a Viessmann boiler: The boiler has a built-in condensate trap. The field drain must be inspectable and must not be fed by other appliances.
Applies to: Vitocrossal 300 CU3A 26 to 199
How to fix install the condensate drain and siphon: step by step
- Remove the condensate siphon from the boiler.
- Fill the siphon with water and reinstall it on the boiler.
- Connect the field drain to the siphon outlet using 3/4 in. diameter discharge tubing (CPVC, PVC or other approved material).
- Install the drain pipe with a suitable downward gradient.
- Terminate the drain into an open or vented drain as close to the boiler as possible to prevent siphoning.
- Ventilate the pipe between the siphon trap and the neutralization unit, if one is used.
- If the boiler condensate outlet is lower than the drain, install a condensate pump approved for condensing boilers, with an overflow switch.
- If the boiler is installed even with the ground, keep the condensate drain no more than 2 in. (50 mm) above ground.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A 26 to 199 installation instructions, p. 22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.