Viessmann Boiler: Install and check the DHW tank temperature sensor
Install and check the DHW tank temperature sensor on a Viessmann boiler: Sensor for single-boiler systems with DHW heating. Do not connect it on systems without DHW heating.
Applies to: Vitotronic 300-K MW1S DHW tank temperature sensor
How to fix install and check the dhw tank temperature sensor: step by step
- Install the DHW tank temperature sensor following the DHW tank installation instructions.
- When fitting the sensor in a tank of another make, press it against the tank's sensor well with a suitable device.
- Make sure the maximum permitted DHW temperature cannot be exceeded; fit a suitable safety device if needed.
- Disconnect the sensor from the terminals and measure its resistance at plug terminals 1 and 2.
- Compare the reading with the tank temperature and replace the sensor if the difference is significant.
- Reconnect the plug after the check. On systems without DHW heating, leave the sensor unconnected.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.