Viessmann Boiler: Install and check the boiler temperature sensor
Install and check the boiler temperature sensor on a Viessmann boiler: The boiler water sensor is fitted with the boiler insulation and plugs into socket 3 on the boiler control. Check it by resistance against the temperature.
Applies to: Boiler temperature sensor, socket 3
How to fix install and check the boiler temperature sensor: step by step
- Disconnect plug in the boiler control terminal compartment.
- Measure resistance at terminals 1 and 2 of the plug.
- Compare the reading with the actual boiler water temperature using the resistance table.
- If the value differs significantly, check the installation and replace the sensor if needed.
- Plug the sensor into socket 3 on the boiler control.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 Installation and Service Instructions, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.