Viessmann Boiler: Inspection and maintenance intervals
Inspection and maintenance intervals on a Viessmann boiler: Service intervals for the boiler, DHW tank and accessories as listed by Viessmann.
Applies to: Vitotronic 300-K system with boiler, DHW tank and potable water filter
How to fix inspection and maintenance intervals: step by step
- Service the heating system at least every 2 years by an authorised contractor.
- Clean the boiler annually, as contamination raises flue gas temperature and energy losses.
- Clean the DHW tank and DHW connections no later than 2 years after commissioning and as needed; only a qualified contractor should clean inside the tank.
- On Vitocell 100 tanks, have the sacrificial anode checked annually with an anode tester.
- Check the DHW tank safety valve every six months by venting it; the outlet must not be closed off.
- Replace the filter element on non-back-flushing potable water filters every six months and inspect it every two months.
- Back-flush back-flushing potable water filters every two months.
- Replace damaged cables or lines only with Viessmann cables or lines through a qualified contractor.
- Clean the controls with a non-scouring domestic cleaning agent and the microfibre cloth supplied.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
MW1SVitotronic 300-K, type MW2B
Source: Vitotronic 300-K MW2C operating instructions, p. 30. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.