Viessmann Boiler: Hydrostatic leak test of the boiler

Updated · by Aurora Star Tech Inc.

Hydrostatic leak test of the boiler on a Viessmann boiler: Test before the boiler is connected to piping or power. Do not exceed 1-1/2 times the maximum operating pressure.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitorond 100 VR1 boilers

How to fix hydrostatic leak test of the boiler: step by step

  1. After installing the safety devices, fit a temporary cap on the 3/4 in. pressure relief nipple.
  2. Cap the supply and return connections.
  3. Connect a 1/2 in. garden hose to the boiler drain valve and fill slowly until the gauge reads 68 psi (4.65 bar).
  4. Hold pressure for 15 minutes. Do not leave the boiler unattended.
  5. Check pipe joints, safety devices and boiler base for leaks with a flashlight.
  6. Release pressure slowly through the drain valve, remove the caps, and install the pressure relief valve.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitorond 100 VR1 installation and service manual, p. 22. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.