Viessmann Boiler: Heating circuit pump economy logic
Heating circuit pump economy logic on a Viessmann boiler: Heating circuit pump switches off (supply set point 32°F (0°C)) when one of the following is met. Requires no frost risk and coding b0 set to 0.
Applies to: Economy heating circuits
How to fix heating circuit pump economy logic: step by step
- Outdoor temperature exceeds the value set in coding a5.
- Adjusted outdoor temperature exceeds the value set in coding a6.
- Mixing valve has tried to close for more than 12 min (coding a7).
- Pump idle time set in coding a9 has elapsed.
- Actual room temperature exceeds the value set in coding b5.
- If heating mode is restarted or set room temperature is raised during idle time, the pump starts immediately.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.