Viessmann Boiler: Heating circuit frost protection
Heating circuit frost protection on a Viessmann boiler: With outdoor temperatures below 34 F / 1 C the control keeps the supply temperature at 59 to 72 F / 15 to 22 C for frost protection. The frost threshold can be changed with coding A3. Setting A3 below 34 F / 1 C risks freezing pipes outside the insulated area, such as roof space, garages and radiator alcoves. Check the insulation of the whole system and watch standby periods such as holidays.
Applies to: Heating circuit frost protection, codings A3 and A4
How to fix heating circuit frost protection: step by step
- Check the insulation of exposed piping before lowering the frost threshold below 34 F / 1 C.
- Set coding A3 to the required threshold value.
- Use coding A4:1 to switch off frost protection only if coding A3:-9 is set.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
Source: Vitotronic 200 KW2 service instructions, p. 48, p. 50. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.