Viessmann Boiler: Heating and cooling piping arrangement

Updated · by Aurora Star Tech Inc.

Heating and cooling piping arrangement on a Viessmann boiler: Boiler piping when the same system also provides chilled water.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitorond 200 VD2A boilers in heating/cooling systems

How to fix heating and cooling piping arrangement: step by step

  1. Pipe the chiller in parallel to the boiler with valves so chilled water cannot enter the boiler.
  2. Fit flow control valves or other automatic means where coils in air handlers may see refrigerated air, to stop gravity circulation of boiler water during cooling.
  3. Set valve V1 open and V2 closed for the heating season; reverse them for the cooling season.
  4. Tag the valves with their purpose.
  5. Run the circulating pump from its own on/off switch, not the boiler pump aquastat.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitorond 200 VD2A installation manual, p. 37. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.