Viessmann Boiler: Gas static pressure check
Gas static pressure check on a Viessmann boiler: Measure the static gas pressure at the boiler inlet with the burner off.
Applies to: Vitocrossal 300 CA3B 2.5 to 6.0
How to fix gas static pressure check: step by step
- Close the gas shut-off valve.
- Loosen the measuring connector screw A. Do not remove it.
- Connect a pressure gauge at measuring connector A.
- Open the gas shut-off valve.
- Measure static pressure. Maximum is 14 in. w.c.
- Record the reading in the maintenance record (p. 162).
- Make sure no open flame is in the room during the check.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
Source: Vitocrossal 300 CA3B service instructions, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.