Viessmann Boiler: Gas shut-off valve connection and electrical supply
Gas shut-off valve connection and electrical supply on a Viessmann boiler: Gas connection sequence at the boiler and the power requirement for the accessory box.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
How to fix gas shut-off valve connection and electrical supply: step by step
- Make gas connections per CAN/CSA B149.1 and .2 or ANSI Z223.1/NFPA 54 and local codes.
- Connect the gas shutoff valve to the boiler gas connection.
- Close the gas shutoff valve on the boiler once it is connected.
- Make sure about 2 threads are left bare at the manual gas shutoff connection.
- Provide a 120 VAC, 12 A supply for the external accessories connection box. Use the wiring diagram on p. 47.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Installation Instructions, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.