Viessmann Boiler: Gas piping pressure test and leak check
Gas piping pressure test and leak check on a Viessmann boiler: Protect the boiler from high test pressures and check the gas train for leaks after it is connected.
Applies to: VD2-320 to VD2-1080
How to fix gas piping pressure test and leak check: step by step
- Install a sediment trap or dirt pocket upstream of all gas controls.
- If the test pressure is above 14 in. w.c. (3.5 kPa), disconnect the boiler and its individual shut-off valve from the gas piping.
- If the test pressure is 14 in. w.c. (3.5 kPa) or less, close the boiler's individual manual shut-off valve to isolate it.
- Connect and size gas supply piping per local and national codes.
- Leak test with an approved liquid spray solution. Never use an open flame. Keep liquid off electrical parts and keep it away from the gas valve regulator and vent opening.
- Purge air from the gas line with an approved purge or vent to outdoors.
- Unions and the gas manifold were not factory tested, so a licensed gas fitter must complete a leak test during initial trial operation.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2 installation manual, p. 35. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.