Viessmann Boiler: Gas piping pressure and leak test
Gas piping pressure and leak test on a Viessmann boiler: Tests above 14 in. w.c. (1/2 psig) require the boiler and its shutoff valve to be disconnected from the supply. At or below that level, isolate the boiler with its manual valve only.
Applies to: Vitodens 200-W B2HB gas piping
How to fix gas piping pressure and leak test: step by step
- For tests at or below 1/2 psig (14 in. w.c.), keep the boiler isolated using its manual shutoff valve.
- For tests above 1/2 psig (14 in. w.c.), disconnect the boiler and its shutoff valve from the gas supply first.
- Perform a leak test with an approved liquid spray solution. Keep it off electrical parts, wires and connectors, and away from the gas valve regulator and regulator vent opening.
- Correct any leaks found and retest.
- Purge air from the gas line.
- Do not check for leaks with an open flame.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HB installation manual, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.