Viessmann Boiler: Gas connection and shutoff valve installation
Gas connection and shutoff valve installation on a Viessmann boiler: Set up the gas supply to the boiler with the required shutoff and drip leg.
Applies to: Vitodens 222-F B2TB
How to fix gas connection and shutoff valve installation: step by step
- Size the gas pipe for pipe length, fittings, gas type and the total input of all gas appliances in the home.
- Confirm the gas line does not drop in pressure when any appliance lights or runs.
- Install a ground joint union, a capped drip leg and a listed manual shutoff valve before the boiler.
- Connect the boiler gas connection (one of three locations) per CAN/CSA B149.1/.2 or NFGC ANSI Z223.1/NFPA 54 and local codes.
- Close the boiler's manual gas shutoff valve once connected.
- Tag the shutoff valves and show the owner where they are.
- Leak test the gas piping before the boiler is put into operation. Never use an open flame to check for leaks.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125
Source: Viessmann Vitodens 222-F B2TB installation manual, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.