Viessmann Boiler: Gas connection and piping
Gas connection and piping on a Viessmann boiler: Connect gas per the national or provincial fuel gas code and local rules. Size the pipe for the whole building, including all appliances.
Applies to: Gas supply piping to Vitodens 100-W WB1B
How to fix gas connection and piping: step by step
- Close the gas shutoff valve on the boiler.
- Install a ground joint union, capped drip leg and manual shutoff valve before the boiler, using nationally listed valves.
- Make the boiler gas connection (3/4 in NPT).
- Support the piping so it does not rest on or hang from the boiler.
- Use moderate pipe dope and leave 2 threads bare.
- Carry out the gas piping leak test, then bleed air from the gas line.
- Label the shutoff valves and show the owner where they are.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 100-W WB1B installation manual, p. 18-19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.