Viessmann Boiler: Frost protection for the supply temperature
Frost protection for the supply temperature on a Viessmann boiler: Below +1°C / 34°F outdoors, the control holds the supply temperature at 15 to 22°C / 59 to 72°F (two-point control). The outdoor threshold can be changed via coding address A3.
Applies to: Heating circuits
How to fix frost protection for the supply temperature: step by step
- Check the outdoor sensor and frost threshold setting A3 if the supply is not held in the 15 to 22°C range.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 88. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.