Viessmann Boiler: Free-standing installation on boiler stand
Free-standing installation on boiler stand on a Viessmann boiler: Use the boiler stand when the boiler is free-standing in the mechanical room. No mounting template is supplied; locations must be calculated in the field.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199 with boiler stand
How to fix free-standing installation on boiler stand: step by step
- Fasten the stand securely to the floor; the recommended concrete expansion anchors are Hilti KB-TZ or equivalent.
- Attach the wall mounting bracket to the boiler mounting frame with the supplied hardware and check it is level.
- Move the frame into position and secure it to the floor, and to the wall if needed.
- Calculate the wall location for the frame, mounting bracket and all vents in the field.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Vitodens 200-W B2HB 45, 57, 160, 199 Installation Instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.