Viessmann Boiler: Flue system conditions before commissioning

Updated · by Aurora Star Tech Inc.

Flue system conditions before commissioning on a Viessmann boiler: Commissioning may only start when the flue and air supply conditions are met.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 100-W B1HE/B1KE flue system

How to fix flue system conditions before commissioning: step by step

  1. Confirm unrestricted flow in the flue gas routes.
  2. Confirm the positive pressure flue system is gas-tight.
  3. Check inspection port covers are secure and tight.
  4. Confirm combustion air openings are open and cannot be closed.
  5. Confirm all local flue and commissioning regulations are followed.
  6. Fit the coaxial vent seal if the boiler is direct vent on a two-pipe system.
  7. Vents for combustion air must be non-closable and wind protected to stop condensate draining.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitodens 100-W, B1HE/B1KE Installation/Service, p. 24. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.