Viessmann Boiler: Flue outlet and flue gas test point
Flue outlet and flue gas test point on a Viessmann boiler: Connect the flue outlet to the chimney and provide a test point for combustion analysis.
Applies to: Vitorond 200 VD2 320 to 1080
How to fix flue outlet and flue gas test point: step by step
- Connect the flue outlet with the shortest possible run, sloping slightly up toward the chimney. Avoid sharp bends.
- The flue outlet is 12 in. (300 mm) outside diameter.
- Drill a test hole of about 10 mm (3/8 in.) in the side of the vent pipe about two to three vent diameters from the boiler flue collar.
- Seal and insulate the vent pipe.
- Make sure the chimney size is designed for the actual boiler model and input. The boiler outlet size does not set the breeching or chimney size.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200, VD2 Series 320 to 1080 Installation Instructions, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.