Viessmann Boiler: Fixed high limit test, simulation #2 (jumpered flow switch, boiler valve closed)
Fixed high limit test, simulation #2 (jumpered flow switch, boiler valve closed) on a Viessmann boiler: Alternate high limit test. Boiler valve closed and flow switch jumpered so the boiler overheats until the fixed high limit trips.
Applies to: Vitodens 200-W B2HA 45, 60 (CSD-1 high limit field test)
How to fix fixed high limit test, simulation #2 (jumpered flow switch, boiler valve closed): step by step
- Close the boiler valve.
- Jumper across the flow switch.
- Run the boiler at high fire. Coding card set to maximum on B2TB models (coding address 06).
- Let the boiler temperature keep rising until the fixed high limit trips.
- Slowly open the boiler valve to cool the boiler down safely.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.