Viessmann Boiler: Fixed high limit test simulation #1
Fixed high limit test simulation #1 on a Viessmann boiler: Tests the fixed high limit by stopping boiler pump flow while the burner is firing. Follow this only where required by law and accept that overheating damage from the test is not covered by Viessmann.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352 (boiler sizes 19 to 100 with flow switches may need the flow switch jumpered)
How to fix fixed high limit test simulation #1: step by step
- Make sure the boiler and boiler pump are in normal operating condition.
- Remove the cover from the back of the boiler control to reach the control plugs.
- Enter flue gas test mode from the extended menu.
- Once the burner ignites, unplug the boiler pump plug marked sÖ from the control board, gently with pliers.
- Watch the boiler temperature on the display. The burner should shut off and temperature should continue to rise.
- When the temperature reaches 210°F (99°C), the manual reset high limit trips and shows an F2 fault.
- If the limit is not reached, repeat the test and, two minutes after the burner shuts off, energize the boiler pump for a maximum of 1 second by plugging in the pump plug.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 service instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.