Viessmann Boiler: Fixed high limit test, simulation #1 (flue gas test with boiler pump unplugged)
Fixed high limit test, simulation #1 (flue gas test with boiler pump unplugged) on a Viessmann boiler: Test of the fixed high limit (manual reset) using the flue gas test mode. Pump plug disconnected to let temperature rise. Observe the temperature and make sure the limit trips.
Applies to: Vitodens 200-W B2HA 45, 60 (CSD-1 high limit field test)
How to fix fixed high limit test, simulation #1 (flue gas test with boiler pump unplugged): step by step
- Make sure the boiler and boiler pump are in normal operating condition.
- Remove the cover at the back of the boiler control to reach the control plugs.
- In the extended menu of the operating manual, select 'Test mode', then 'flue gas test ON', and press OK.
- Wait for the burner to ignite and go to high fire.
- Once the burner is lit, carefully unplug the boiler pump plug sÖ from the control board.
- Watch the boiler temperature on the display. The burner will shut off, then the temperature should keep rising.
- At 210°F (99°C) the manual reset high limit should trip and give an F2 fault.
- If the limit is not reached, repeat with one extra step: two minutes after burner shut-off, plug the pump back in for no more than 1 second.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.