Viessmann Boiler: Fixed high limit test (per boiler section)
Fixed high limit test (per boiler section) on a Viessmann boiler: Each boiler section has its own fixed high limit and each must be tested individually. The test raises the boiler water temperature until the fixed limit trips, so the boiler must be watched closely. Viessmann is not responsible for damage caused by overheating during this test.
Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
How to fix fixed high limit test (per boiler section): step by step
- Use the emission test switch on the boiler section to start a call for heat.
- In menu 6 of that section's burner control (GC310), item 4, temporarily raise the max boiler water temperature to 243°F (117°C) so it is above the fixed limit.
- Press the emission test switch for the section so the burner starts.
- Slowly throttle the water flow to the boiler.
- Watch the temperature on the GW6C service display.
- When the fixed high limit trips, the control hard locks out with F F2 displayed. The fan runs for 10 minutes.
- Reset the fault only after the water temperature has dropped.
- Restore the original menu 6 item 4 setting.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.