Viessmann Boiler: Fixed high limit test, method 2 (CSD-1)
Fixed high limit test, method 2 (CSD-1) on a Viessmann boiler: Second way to test the fixed high limit by running the boiler at high fire with no flow. Only do this where required by law.
Applies to: Vitodens 200-W B2HA 112/150/399/530
How to fix fixed high limit test, method 2 (csd-1): step by step
- Close the boiler valve.
- Jumper across the flow switch.
- Run the boiler at high fire. Set coding address 06 to maximum on B2TB models so the coding card runs it at high fire.
- Keep the boiler temperature rising until the fixed high limit trips.
- Once it trips, slowly open the boiler valve to cool the boiler down safely.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Viessmann Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.