Viessmann Boiler: Fixed high limit test #2 (valve closed, flow switch jumpered)
Fixed high limit test #2 (valve closed, flow switch jumpered) on a Viessmann boiler: Alternate high limit test. The boiler is run at high fire with the boiler valve closed. Jumpering the flow switch may be needed for testing. Only do this where required by law.
Applies to: Models 112, 150, 399, 530
How to fix fixed high limit test #2 (valve closed, flow switch jumpered): step by step
- Close the boiler valve and jumper across the flow switch.
- Run the boiler at high fire. The boiler should shut down by the coding card (on B2TB models, set coding address 06 to maximum) but keep heating until the fixed high limit trips.
- After the fixed high limit trips, slowly open the boiler valve to cool the boiler down safely.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.