Viessmann Boiler: Fixed high limit test #2 (flow switch jumpered)
Fixed high limit test #2 (flow switch jumpered) on a Viessmann boiler: Alternative test that trips the fixed high limit with the boiler valve closed and the flow switch jumpered. Only do this with the boiler monitored and under control.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
How to fix fixed high limit test #2 (flow switch jumpered): step by step
- Close the boiler valve and jumper across the flow switch.
- Run the boiler at high fire. For B2TB models, set coding address 06 to maximum to hold high fire.
- Let the temperature keep rising until the fixed high limit trips.
- Slowly open the boiler valve to cool the boiler down.
- Remove the jumper and restore normal operation.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.