Viessmann Boiler: Fixed high limit test #1 (boiler pump disconnected)
Fixed high limit test #1 (boiler pump disconnected) on a Viessmann boiler: CSD-1 field test of the fixed high limit using the boiler pump. Manufacturer disclaims damage from overheating during this test.
Applies to: Vitodens 200-W B2HA 45, 60 (boiler sizes with boiler pump plug)
How to fix fixed high limit test #1 (boiler pump disconnected): step by step
- Confirm the boiler and boiler pump are in normal operating condition.
- Remove the back cover of the boiler control to reach the control plugs.
- In the extended menu, select Test mode, then flue gas test ON, and press OK.
- Wait for the burner to ignite and go to high fire.
- Once the burner ignites, carefully unplug the boiler pump plug from the control board.
- Watch the boiler temperature rise and the burner shut off.
- Confirm the boiler temperature keeps rising until the manual reset high limit trips at about 210°F (99°C), giving an F2 fault.
- If the limit is not reached, wait two minutes after burner shutoff, then plug the pump in for a maximum of 1 second. Repeat as needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.