Viessmann Boiler: Fill heating system with water
Fill heating system with water on a Viessmann boiler: Flush the system before filling and use potable-quality water. Soften the water if it is harder than 8.77 grains / 150 ppm total dissolved solids. Use only inhibitors or antifreeze made for hot water heating. Do not use automotive silicate antifreeze.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
How to fix fill heating system with water: step by step
- Thoroughly flush the entire heating system before filling.
- Confirm all necessary flow check valves are installed and system isolation valves at C and D are open (if installed).
- Check the expansion tank precharge against static pressure before filling.
- Fill the system at the boiler fill (BF) and bleed air fully from the boiler drain (BD).
- If using antifreeze, use 40% for protection to -10°F (-23°C) and follow the manufacturer specifications.
- Check the total system frequently when filled with antifreeze.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Viessmann Vitodens 200-W B2HB 45, 57, 160, 199 service instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.