Viessmann Boiler: Field wiring to digital inputs and low-voltage outputs

Updated · by Aurora Star Tech Inc.

Field wiring to digital inputs and low-voltage outputs on a Viessmann boiler: Keep the separation required for external contacts and the 0-10 V input.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: EA1 extension module and external connections

How to fix field wiring to digital inputs and low-voltage outputs: step by step

  1. For external contacts, observe safety category II: 8.0 mm air gap and creep path, or 2.0 mm insulation thickness against live parts.
  2. Ensure DC separation between the LV output and the earth conductor of the on-site voltage source when using the 0-10 V input.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300

More other tips for boiler

Source: Vitotronic 200-H HK1B installation and service instructions, p. 77. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.