Viessmann Boiler: Field test the fixed high limit (CSD-1, where required by law)
Field test the fixed high limit (CSD-1, where required by law) on a Viessmann boiler: Viessmann is not responsible for damage the test can cause by overheating the system. Three simulations are described. Simulation 1 and 2 test the fixed high limit with the burner running. Simulation 3 tests the control fault produced by a wiring fault on the limit.
Applies to: Vitodens 200-W B2HA boilers where CSD-1 testing is required
How to fix field test the fixed high limit (csd-1, where required by law): step by step
- Simulation 1: close the boiler valve and jumper across the flow switch.
- Simulation 1: run the boiler at high fire. The boiler should shut down via the coding card (on B2TB models set coding address 06 to maximum), but the temperature should keep rising until the fixed high limit trips.
- Simulation 1: once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down safely.
- Simulation 2: throttle the boiler valve so the burner runs with as little flow as possible.
- Simulation 2: run the boiler to high fire using the relay test.
- Simulation 2: when the burner shuts down on the electronic limit, close the ball valve to stop the flow.
- Simulation 2: the boiler temperature should continue to rise and trip the fixed high limit.
- Simulation 2: once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down safely.
- Simulation 3: disconnect one of the wires on the limit switch. This produces a control fault that needs a manual reset.
- Confirm the boiler locks out and requires manual reset after each simulation.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA service instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.