Viessmann Boiler: Field test of fixed high limit (CSD-1)
Field test of fixed high limit (CSD-1) on a Viessmann boiler: Where required by law, the fixed high limit can be tested in the field. The manufacturer is not responsible for damage caused by overheating during this test. The fixed high limit trips a fault that needs a manual reset.
Applies to: Vitodens 200-W B2HA 19, 28, 35
How to fix field test of fixed high limit (csd-1): step by step
- Simulation #1: close the boiler valve and jumper across the flow switch.
- Simulation #1: run the boiler at high fire. In B2TB models set coding address 06 to maximum. The burner shuts down on the coding card but the temperature keeps rising until the fixed high limit trips.
- Simulation #1: once the fixed high limit trips, slowly open the boiler valve to cool the boiler.
- Simulation #2: throttle the boiler valve so the burner runs with as little flow as possible.
- Simulation #2: run the boiler to high fire using the relays test.
- Simulation #2: when the burner shuts down on the electronic limit, close the ball valve to stop the flow.
- Simulation #2: the temperature should keep rising until the fixed high limit trips. Then slowly open the boiler valve to cool down.
- Simulation #3: remove one wire from the limit switch. This creates a fault that requires manual reset.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 200-W B2HA service instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.