Viessmann Boiler: External safety and disable connections
External safety and disable connections on a Viessmann boiler: Jumpers on the line voltage motherboard must be removed before external safety equipment or an external disable is wired in.
Applies to: Vitotronic 100 GC1 line voltage motherboard
How to fix external safety and disable connections: step by step
- Remove the jumper at terminal a before connecting external safety equipment.
- Remove the jumper at terminal b before connecting an external disable.
- Connect the external burner activation at terminal c as needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 300-K MW1S installation and service manual, p. 171. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.