Viessmann Boiler: External heating program changeover
External heating program changeover on a Viessmann boiler: A dry contact changes the heating program. At plug avD, coding 91 (General group) assigns the function to the heating circuits. With extension EA1, set 5D, 5E or 5F to 1, and use coding D8 in the heating circuit group. The changeover can be set separately for heating circuits 1 to 3.
Applies to: Heating program changeover
How to fix external heating program changeover: step by step
- Use a potential-free dry contact.
- At plug avD, set coding 91 (General group) to assign the function to the heating circuits.
- With extension EA1, set 5D, 5E or 5F (General group) to 1.
- Set coding D8 in the heating circuit group if using EA1.
- Set changeover separately for heating circuits 1 to 3 as needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitotronic 200
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
Vitotronic 300-K
MW1SVitotronic 300-K, type MW2B
Source: Vitotronic 200 and 300-K Installation and Service, p. 22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.