Viessmann Boiler: External demand
External demand on a Viessmann boiler: External contact requests heat and can enforce a minimum boiler water temperature.
Applies to: Vitodens 200-W B2HA 80 to 100
How to fix external demand: step by step
- Wire the floating contact to DE1, DE2 or DE3.
- Set the input to 3A:2, 3B:2 or 3C:2.
- Set pump response with 3F (internal pump), D7 (heating circuit pump) and 5F (DHW circulation pump).
- Set the minimum set boiler water temperature with 9B.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HA Service Instructions, p. 90. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.