Viessmann Boiler: External demand via dry contact
External demand via dry contact on a Viessmann boiler: A closed dry contact runs the burner load-dependent. Supply water is heated to the set value in coding address 9B (General group) on the Vitotronic 300-K, and is limited by the boiler supply temperature maximum set in coding address 06 (Boiler group) on the Vitotronic 200. Connect the contact to plug aVH (no code needed) or to extension EA1 (accessory).
Applies to: External demand contact
How to fix external demand via dry contact: step by step
- Use a potential-free dry contact. Live contacts cause shorts or phase failure.
- Connect to plug aVH (no code needed), or to extension EA1.
- If using extension EA1, set coding 5D, 5E or 5F (General group) to 2.
- Set coding 9B to the required supply water temperature.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitotronic 200
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
Vitotronic 300-K
MW1SVitotronic 300-K, type MW2B
Source: Vitotronic 200 and 300-K Installation and Service, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.