Viessmann Boiler: External boiler activation contact (isolation valve open/closed)

Updated · by Aurora Star Tech Inc.

External boiler activation contact (isolation valve open/closed) on a Viessmann boiler: Dry contact at plug aVH controls boiler activation. Essential on multi-boiler systems. Lead boiler contact must stay closed.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: VD2/VD2A/CT3/CM2

How to fix external boiler activation contact (isolation valve open/closed): step by step

  1. Connect a dry contact to terminals 2 and 3 of plug aVH.
  2. Contact closed: preheat for follow-up boilers runs first (coding 2b). Then minimum temperature is held and burner stages can be switched externally. Setpoint is chosen with coding 9b.
  3. Contact open: isolation valve closes after about 5 minutes (coding 2C). No external burner override and no minimum temperature is held.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

GC1KW10B

Source: Vitotronic 100, GC1 installation manual, p. 60. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.