Viessmann Boiler: External blocking via dry contact
External blocking via dry contact on a Viessmann boiler: A closed contact shuts the burner down and switches off the boiler circuit pumps. The system has no frost protection while blocked, and the boiler is not held at its lower water temperature. Connect to plug avD (code 99, General group) or to extension EA1 (set 5D, 5E or 5F to 3 or 4). Optional temperature range settings are in coding address 1E.
Applies to: External blocking contact
How to fix external blocking via dry contact: step by step
- Use a potential-free dry contact.
- Connect to plug avD and set coding 99 (General group), or connect to extension EA1.
- If using EA1, set 5D, 5E or 5F (General group) to 3 or 4.
- Warn the owner that frost protection is off while blocked.
- For optional temperature range settings, check coding address 1E.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitotronic 200
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
Vitotronic 300-K
MW1SVitotronic 300-K, type MW2B
Source: Vitotronic 200 and 300-K Installation and Service, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.