Viessmann Boiler: External 0-10 V signal connection for boiler water setpoint

Updated · by Aurora Star Tech Inc.

External 0-10 V signal connection for boiler water setpoint on a Viessmann boiler: A 0-10 V signal from an external controller sets the maximum boiler water temperature. Example from the manual: 8 VDC equals 176 ºF (80 ºC). The full voltage-to-temperature chart is not on these pages.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA 80-100, 285-352 with EA1 module

How to fix external 0-10 v signal connection for boiler water setpoint: step by step

  1. Connect the external 0-10 V signal to the 0-10V plug on extension module EA1.
  2. Check the polarity.
  3. Use the chart in the manual to find the required signal for the desired maximum water temperature.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 installation instructions, p. 51. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.