Viessmann Boiler: External 0-10 V boiler water temperature setpoint
External 0-10 V boiler water temperature setpoint on a Viessmann boiler: An external 0-10 V signal sets the maximum possible boiler water temperature. The voltage-to-temperature chart is not reproduced on this page, only one example.
Applies to: Vitocrossal 300 CU3A 26 to 199, extension module EA1
How to fix external 0-10 v boiler water temperature setpoint: step by step
- Connect the external 0-10 V signal to the 0-10V plug on extension module EA1.
- Check that the polarity is correct.
- Use the chart to match the signal voltage to the maximum boiler water temperature.
- Example: 8 VDC equals 176 ºF (80 ºC).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A 26 to 199 Installation Instructions, p. 33. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.