Viessmann Boiler: Enlarge burner opening for Carlin EZ-LF-1HP
Enlarge burner opening for Carlin EZ-LF-1HP on a Viessmann boiler: Required when installing the Carlin EZ-LF-1HP burner.
Applies to: Carlin EZ-LF-1HP burner
How to fix enlarge burner opening for carlin ez-lf-1hp: step by step
- Enlarge the burner opening from 3-1/2 in. to a maximum of 4-1/2 in.
- Trim the door refractory and insulation material to make the opening.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 VR1 installation and service manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.