Viessmann Boiler: DHW tank piping and pump check
DHW tank piping and pump check on a Viessmann boiler: Undersized DHW piping or a pump with too little head can cause short-cycling and poor DHW supply. Non-Viessmann tanks need a coil pressure drop check against pump head.
Applies to: DHW tank installations
How to fix dhw tank piping and pump check: step by step
- Size DHW supply and return piping to the minimum pipe size for the model.
- On non-Viessmann tanks, calculate DHW coil pressure drop against the field pump's residual head.
- Confirm the tank sensor with the tank maker if the tank is not Viessmann Vitocell 100 or 300.
- Install a temperature tempering valve in the DHW supply line.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
More commissioning tips for boiler
Source: Vitodens 200-W, B2HB technical data manual, p. 33. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.