Viessmann Boiler: DHW piping size and flow with non-Viessmann tanks
DHW piping size and flow with non-Viessmann tanks on a Viessmann boiler: DHW supply and return piping between the boiler and the tank must be at least 1¼ in. so the field pump's residual head is used well. A non-Viessmann tank needs a coil pressure drop check against the pump head. Undersizing can cause short-cycling and poor DHW supply.
Applies to: Vitodens 200-W B2HA 45, 60 DHW installations
How to fix dhw piping size and flow with non-viessmann tanks: step by step
- Install DHW supply and return piping of at least 1¼ in. between boiler DHW connections and the Viessmann tank connections.
- For a non-Viessmann tank, calculate the tank coil pressure drop against the boiler pump residual head.
- Confirm enough water flow reaches the boiler heat exchanger before commissioning.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Vitodens 200-W B2HA 45, 60 installation manual, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.