Viessmann Boiler: CSD-1 fixed high limit test, simulation #2 (closed boiler valve)

Updated · by Aurora Star Tech Inc.

CSD-1 fixed high limit test, simulation #2 (closed boiler valve) on a Viessmann boiler: Alternate field test of the fixed high limit with the boiler valve closed. Overheating is possible.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA boilers, where required by law

How to fix csd-1 fixed high limit test, simulation #2 (closed boiler valve): step by step

  1. Close the boiler valve.
  2. Jumper across the flow switch.
  3. Run the boiler at high fire. On B2TB models, set coding address 06 to maximum.
  4. Keep the boiler running until the fixed high limit trips.
  5. Once the limit has tripped, slowly open the boiler valve to cool the boiler down.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitodens 200-W B2HA installation manual, p. 7. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.