Viessmann Boiler: CSD-1 fixed high limit field test (simulation #2)
CSD-1 fixed high limit field test (simulation #2) on a Viessmann boiler: Alternate CSD-1 high limit test using the relays test and a throttled boiler valve.
Applies to: Vitodens 200-W B2HB, all models
How to fix csd-1 fixed high limit field test (simulation #2): step by step
- Throttle the boiler valve so the burner runs with as little flow as possible.
- Run the boiler to high fire using the relays test.
- When the burner shuts down on the electronic limit, close the ball valve to stop the flow.
- Confirm the boiler temperature keeps rising until the fixed high limit trips.
- Once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down safely.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.