Viessmann Boiler: CSD-1 fixed high limit field test (simulation #1)

Updated · by Aurora Star Tech Inc.

CSD-1 fixed high limit field test (simulation #1) on a Viessmann boiler: Field test of the fixed high limit where required by law. Viessmann is not responsible for damage caused by overheating the system during this test.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HB, all models

How to fix csd-1 fixed high limit field test (simulation #1): step by step

  1. Close the boiler valve and jumper across the flow switch.
  2. On B2HB models, set coding address 06 to maximum on the coding card.
  3. Run the boiler at high fire. It will shut down from the coding card but the boiler temperature should keep rising until the fixed high limit trips.
  4. Once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down safely.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 7. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.